REPORT OF OBSERVATION AND FIELD DENSITY TESTING
ROUGH GRADING
Single Family Residential Development
Lot 21, Tract No. 3646
NEC East Vallejo Avenue & Ynez Road
Temecula, California
-
PROJECT NO. 22291-01
June 13, 2002
Prepared For:
Linda Doucett
2170 Century Park E. No. 307
Los Angeles, California 90067
\
Earth Technics P.O. Box 891989, Temecula, California 92589 (909) 699-5451 FAX (909) 767-1193
June 3, 2002
project No. 22291-01
Linda Doucett
2170 Century Park E. No. 307
Los Angeles, California 90067
SUBJECT: REPORT OF OBSERVATION AND FIELD DENSITY TESTING
ROUGH GRADING
single Family Residential Development
Lot 21, Tract No. 3646
NEC East vallejo Avenue , Ynez Road
Temecula, california
Reference: "Preliminary Soil Engineering Evaluation for
Proposed Residence Located at East Vallejo Road
and Ynez Road, City of Temecula, Califoria",
Report Dated December 30, 1999, by W.C. Hobbs
Consulting Engineer, Proj. No. 99128-01
INTRODUCTION
<
This report presents the results of our observation and testing
performed during construction and grading for the single-family
residential development, detached garage, barn, and
appurtenances.
Grading was performed at the northeast corner of East Valejo
Avenue and Ynez Road, both improved paved roads in the Temecula
area of Riverside County. The results of our Field Density Tests
obtained during grading are tabulated in Table I, Results of
Compaction Tests. The approximate locations of the tests are
shown on the Plot Plan, Plate 1. The 40-scale Grading Plan and
Erosion Control Plan were prepared by Vandenberg Civil
Consulting, Canyon Lake, dated April 2002, and were used to plot
our data and guide the grading, along with field staking.
1.1 Pro;ect Description
The proposed development consisted of daylight cutting the house
and detached garage pad approximately 3-5 feet from the north
side of the site. The excavated material was placed as fill to a
maximum depth of 2-3 feet on the south side of the pad. The
access driveway required fills to a maximum of 2 feet. All cut
and fill slopes were constructed at finished face inclinations of
2:1 (horizontal to vertical) or flatter.
1.2 Purpose of Gradinq
The purpose of the grading was to prepare a building pad for the
1 & 2-story residential house, detached garage, and barn, and to
provide a driveway access to the pads from East Vallejo Avenue.
'1/
INDEX. MAP
.
o
2000
4000
SCALE
INDEX r-1Ap
OF
LOT 21, TRACT NO. 3646
NEC YNEZ ROAD & E. VALLEJO AVE.
TEMECULA, CALIFORNIA
feet
2
SOURCE: U.S.G.S. 7~ MIN. QUAD. PECHAr~GA 1968 (PR 1988) & TEMECULA 1968 (PR 1975)
~
.,
N
~
22291-01
Page 3
2.0 GRADING PROCEDURES
2.1 Gradinq Procedures
The entire pad area was cleared and grubbed, and the material
removed off-site. The pad areas were overexcavated through the
loose near-surface colluvium to a maximum depth of 3.8 feet until
the dense underlying sedimentary bedrock with in place densities
of 90% relative compaction was encountered. The fill materials
were brought to near optimum moisture utilizing a 4000-gallon
water truck when necessary. The fill was compacted with a
combination of caterpillar 550G front-end loader, JD850C
bulldozer, and 322L excavator.
The pads were graded entirely in fill overexcavation and all
transitions were removed.
The grading contractor was GSI Construction, Temecula.
3.0 TESTING
3.1 Field Densitv Testinq
Field density testing was performed in accordance with ASTM
D1556-64 (Sand Cone Method). The elevations and the results of
the field density tests are presented in Table I of this report.
The approximate location of the tests are shown on the Grading
Plan, Plate 1.
3.2 Maximum Densitv Determinations
Maximum density/optimum moisture determinations were made from
representative samples of on-site soils used in the fill
operations. The tests were performed in accordance with ASTM D
1557-00 which consist of compacting 5 equal layers of soil in a
1/30 cubic foot volume mold with 25 blows of a 10 pound hammer
falling 18 inches. The results of the Maximum density/optimum
determination are presented herein as Table II, Laboratory Test
Results.
~
22291-01
Page 4
3.3 Expansion Testinq
A finished grade sample was obtained and tested for expansion
utilizing the U.B.C. 29-2 method. The test yielded an expansion
index (E.I.) of 16 which is low expannsion per UBC Table 18-1-B.
3.4 Sulfate Testinq
A finished grade sample was obtained and tested for water
soluable sulfate. The results were below the limits of detection
at 56ppm indicating normal Type II - 2500 psi concrete may be
used for foundations and slabs.
3.5 Settlement
Based on the grading performed, the compaction and soil strength
values, total settlement would be less than 3/4 inch with less
than 1/2 inch differential settlement between footing of similar
size construction and loads over a horizontal distance of 50
feet.
3.6 Foundation Recommendations
The footings will be founded entirely within dense engineered
fill with very low expansion potential. Accordingly, and in
compliance with the recommendations of the referenced report, the
structures may utilize continuous or isolated pier footings with
an allowable maximum bearing capacity of 2000 psf. All exterior
footings shuld be founded a minimum of 18 inches for 1-story and
24 inches for 2-story footings as measured from nearest adjacent
grades.
This value may be increased by one-third for short term wind and
seismic loading conditions.
The foundation should have a minimum of two No. 4 bars top and
bottom for a total of 4 bars as reinforcement. The slab may
utilize No. 3 bars on 18-inch centers as reinforcement. A
moisture barrier should consist of a 10-mil polyethylene vapor
barrier sandwiched between a 1-inch layer of sand top and bottom
to prevent puncture of the barrier and enhance curing of the
concrete.
s
22291-01
Page 5
4.0 SUMMARY
Our description of grading and backfill operations, as well as
observations and testing services, were limited to those grading
operations performed between June 4 and 12, 2002. The
conclusions and recommendations contained herein have been based
upon our observation and testing as noted. To the best of our
knowledge, the work preformed in the areas denoted, has been
accomplished in accordance with the recommendations of the
referenced report, the U.B.C. Appendix Chapter 33, the city of
Temecula Grading Code, and the requirements of the regulating
agencies and is acceptable for its intended purpose.
The cut and fill slopes are stable as constructed. The cut slopes
are composed of sedimentary bedrock, and are stable as
constructed.
No conclusions or warranties are made for areas not tested or
observed. This report should be considered subject to review by
the controlling authorities.
This opportunity to be of service is sincerely appreciated. If
you have any questions, please call.
b
22291-01
Page 5
FJ/WLS:ss
Attachments:
rling
Geotechnical services
Index Map (2000-scale) - Page 2
Plate 1 - Test Location Plan (In Pocket)
Table I - Results of Compaction Tests
Table II - Summary of Maximum Density Testing
Distribution: Addressee (3)
1
TABLE I
>~
RESULTS OF COMPACTION TESTS
JOB NO. 22291-01
NAME: DOUCEIT
DATE: 6/12/02
TEST DATE DEPTH MOISTURE UNIT DRY RELATIVE SOIL DESCRIPTION
NO . CONTENT DENSITY COMPACTION TYPE
(%) (PCF) (%)
1 6/4/02 1023 6.4 131.5 99.0 B BOITOM, OVER-X
BARN PAD
2 6/5/02 1024 10.8 120.3 95.2 A FILL, BARN PAD
3 6/5/02 1025 10.0 122.2 96.7 A FILL, BARN PAD
4 6/6/02 1024 5.6 128.3 96.6 B BOITOM, OVER-X
HOUSE PAD
5 6/7/02 1027 9.3 130.9 98.6 B FILL, BARN PAD
6 6/10/02 1025 10.5 120.6 95.4 A FILL, HOUSE PAD
7 6/10/02 1026 6.1 127.7 96.2 B BOITOM, OVER-X
GARAGE PAD
8a 6/10/02 1027 8.3 108.0 85.4 A test failed, see retest 8b
8b 6/10/02 1027 9.6 120.2 95.'1 A FILL, HOUSE PAD
9a 6/11/02 1028 6.8 116.8 88.0 A test failed, see retest 9b
9b 6/11/02 1028 9.1 125.2 94.3 A FILL, GARAGE PAD
10 6/11/02 1029 8.0 125.3 94.3 B FILL, HOUSE PAD
11 6/12/02 1030.0 10.0 120.7 95.5 A PAD OVER FINISH
12 6/12/02 1029.5 9.6 116.4 92.1 A PAD OVER FINISH
13 6/12/02 1028.5 8.1 128.1 96.4 B PAD OVER FINISH
See plan for test locations.
SC-Sand Cone ASTM 01556-64
.*Test Failed. See Retest.
DC-Drive Cylinder ASTM 02937-71
N-NucIear ASTM 3017-78
~
TABLE II
.>~C.
LABORATORY TEST RESULTS
JOB NO. 22291-01
NAME: DOUCEIT
DATE: 6/12/02
SOIL TYPE; CLASSIFICATION MAXIMUM OPTIMUM
, DENSITY (pFC) MOISTURE (%)
A YELLOW SLIGHTLY SILTY FINE TO 132.8 9.2
COARSE SAND WITH A TRACE OF
GRAVEL
B LIGHT BROWN SILTY SAND WITH A 126.4 10.8
TRACE OF GRAVEL
Ov