REPORT of OBSERVATION
and FIELD DENSITY TESTING
for RESIDENTIAL GRADING
Lot 239; TR 3883
APN: 909-180-006
Temecula, California
Permit # LD98-127GR
February 5, 1999
Prepared for:
Mr. Craig Davis
42205 Rubicon Circle
Temecula, California 92591
(909) 699-2156
Prepared by:
Gunvant Thakkar, P.E.
45712 Classic Way
Temecula, California 92592
(909) 676-7541
.
.,.~ ~
Le'\ 289
RECEIVED
MAR 0 9 1999
CITY OF TEMECULA
ENGINEERING DEPARTMENT
\
.
.
I ;
GUNVANT THAKKAR,
PROFESSIONAL ENGINEER
45712 Classic Way, Temecula, California 92592 (909) 676-7541
February 5, 1999
Mr. Craig Davis
42205 Rubicon Circle
Temecula, California 92591
Phone: 909/699-2156
SUBJECT: Compaction Testing and Report
Lot 239; TR 3883
APN: 909-180-006
Temecula, California
Dear Mr. Davis:
I.
In accordance with your request, we have prepared this rough grading report for the subject
property. The report represents a summary of the observations and compaction testing of the fill
placed on the proposed grading pad. Field testing and observations indicate the compaction of the
soil was performed properly. The soil should perform satisfactorily for the expected usage. The
included findings and recommendations have been derived in accordance with generally accepted
professional principles and practices in the fields of soil mechanics and foundation engineering.
This warranty is in lieu of all other warranties, either expressed or implied.
The opportunity to be of continued services is sincerely appreciated. If you should have any
questions or require further information, please contact me at your convenience.
Respectfully submitted,
~---/2~..--
. 02-
Gunvant Thakkar, RCE 52856
2-.
.
.
INTRODUCTION
In accordance with your request, tests have been performed on the fill placed on the rough graded
residential pad. The excavation, fill placement, compaction and testing associated with this phase
of the, grading was performed during February 22, 1999 through February 26, 1999. This report
presents a summary of the observations and testing services provided.
PROJECT DESCRIPTION
The site will have a single family residence with attached garage constructed on it with associated
landscaping and access drive. This structure could consist of a one or two story, wood framed
residence founded on a continuous perimeter footings foundation system.
GRADING PROCEDURES
The observations and test results indicated that the grading was performed in the method
consistent with the project specifications. All areas to receive fill were striped and cleared of
vegetation and soft soil prior to placement of soil fill.
Keying and benching into natural ground was completed in general compliance with the Uniform
Building Code, as amended by Ordinance 93-04.
The minimum acceptable degree of compaction content was 90 percent of the maximum density.
,
FIELD DENSITY TESTING
Field density testing was performed in accordance with ASTM D1556-64 (Sand Cone Method) or D-
2937-71 (Drive Cylinder) test method, respectively. The results of the field density tests are
presented in Table I of this report. The approximate location of the tests are shown on the Plot
Plan, Plate 1.
MAXIMUM DENSITY DETERMINATIONS
Maximum density/optimum moisture determinations were made from representative samples of on-
site soils used in the fill operations. The tests were performed in accordance with ASTM D1557-78
Method.
.3
.
.
LIMITATIONS
The findings and recommendations of this report were prepared in accordance with contemporary
principles and practices in the field of geotechnical engineering. No other warranty or guarantee is
eithen expressed or implied. Only a portion of the subsurface soils and conditions were evaluated
or observed and the conclusions are based upon an interpretation of the soil conditions
encountered in the field tests. Conclusions are also based on the assumption that these findings do
not vary appreciably in the adjacent areas. However, minor variations may occur: should soil
conditions significantly different be encountered in the future, an assessment of the impact on
subsequent recommendations should be made.
All future grading and fill placement should be performed under the inspection and testing of a
registered civil engineer.
SUMMARY
Our description of grading and backfill operations, as well as observations and testing services,
were limited to those,grading operations performed during February 22,1999 through February 26,
1999. The conclusions and recommendations contained herein have been based upon our
observation and testing as noted. It is our opinion that the work performed in the areas denoted has
generally been accomplished in accordance with Uniform Building Code, as amended by Ordinance
93-04. No conclusions or warranties are made for areas not tested or observed.
Due to periodic site inspections and testing, footing excavations should be inspected by a registered
civil engineer prior to' concrete placement to verify proper embedment entirely into competent soils.
./----
Sinceg!(y,
, ~,
/ .:2?j:~.- \.-
;fEar;:;;., .".. .... ," ....: .
~.v"'"...Jt.;~,(;:'o.2.1 .
Gu~w-ant Tl1ilkkar j "!'
RC~28'56 ,. ,/'
~>.c:(- :=~~"S>:;:. ' -
-,'t;" if:
4.
,"
.
~-:>
.
, ~
6'/...., \ ~
~ ~
<:~
~
q~ lJ..
-...J ....
~
V) ~
'tl
C7;Y 2?~N~ ~
\J
~
~ .
~
-
,
,~
DATE: 2-5"'-8
DalJ;r :S
PLATE: f
SITE LOCATION PLAN
.-
.~
I
~
r
,.0) I
.1
~\
..
~ f"
~
r.
r ~
,\'
! ,~
I
5
/ \ ,
, ~
!'"
\~
PliO fLE. ,
Ff. ELf[ -
~II.
{~
I-
~ I
::-:-/
"..
I
" ,
l'~
, .'>
\ ~
! ~
I
1,1
I
j,
I~
I 1"
,I
/
JV'J76tU'l$ =13.8C'
C(}/YC, b,e",~ I'JI'PI'o/lCH
pCR CITY ()F rEl'E.aJt/l
.~ ~
~
~I ~,
~
f{oteTc ~
,
" ~
:;: ,
" ~
~ ~I
o
LEGEND
. APPROXIMATE TEST LOCATION
DATE: z- 5-9')
Davi1
PLATE: 2
TEST LOCATION
PLAN
.
.
.
i
GUNVANT THAKKAR, PROFESSIONAL ENGINEER
45712 Classic Way, Temecula, California 92592 (909) 676-7541
Mr. Craig Davis
Date Eleva- Max,Dry Water Dry Relative Method
of tion Density Content Density Compac-
Test (Feet) (pcf) (%) (pcf) tion (%)
1, 02/22/99 Key 130,0 9.6 118,3 91 SC
2, 02/22 Key 130,0 9,8 119,6 92 SC
3. 02/23 2 130,0 9,9 117,0 90 SC
4. 02/23 4 130.0 9,8 119.6 92 SC
5. 02/24 6 130.0 9,5 120.9 93 SC
6. 02/24 7 130.0 10,1 119.6 92 SC
7. 02/25 10 130.0 9,8 118.3 91 SC
8, 02/26 FS 130.0 9.5 118.3 91 SC
9, 02/26 FS 130.0 9.4 119.6 92 SC
'\