COMPACTION TEST REPORT
FOR THE PROPOSED RESIDENTIAL DEVELOPMENT
LOT 81, TRACf 3883, A.P.N 919-071-003
LOCATED AT 40685 CARMEI.JTA CIRCLE
TEMECULA, CALIFORNIA
JOB NO. 2208-CI-95
MAY 1, 1995
PREPARED FOR:
C/O MR. BILL BRUSKE
40685 CARMELITA CIRCLE
TEMECULA, CA 92591
(909) 780-0750
10,000 INDIANA AVENUE, SUITE 2 . RIVERSIDE, CA 92503
PHONE (909) 688-8401 . FAX (909) 688-2217
,
"
;
,
,~
,
..
'~
-~
i
~
CLIENT:
JtTTENTION:
, SUBJECT:
I REFERENCES:
DEAR MR. BRUSKE :
.
.
JOB NO.: 2208-CI-95
DATE: MAY 1, 1995
C/O MR. BILL BRUSKE
40685 CARMELITA CIRCLE
TEMECULA, CALIFORNIA 92591
MR. BILL BRUSKE
..
Compaction Test Report for the Proposed
Residential Development, Lot 81, Tract 3883 , A.P.N
919-071-003 located at 40685 Carmelita Circle,
Temecula, California.
1)
Plot plan for the subject site prepared by Art Ramirez, dated
August 2, 1994
In accordance with your authorization, we have performed field density testing during
March 31, April 3 and 4, 1995 for the subject project. The approximate locations of the
field density tests are shown on the plot plan. The plot plan was based on the plot plan
submitted by your office.
A brief summary of the field density testing operations, test results, and other
pertinent information are presented in the following report.
This report should be reviewed in detail prior to proceeding with the planed
development of the project.
1 OF 6
2-
DATUM GEOTECHNICAL
CONSULTANTS. INC.
.
..
JOB NO.: 2208-CI-95
DATE: MAY 1, 1995
This opportunity to be of service is appreciated, should you have any questions
regarding this report, please do not hesitate to contact this office.
Respectfully,
DATUM GEOTECHNICAL CONSULTANTS, INC.
. 0'
r
"IS#1"-"-.:J A. ~
Ismail A. Hadi,P. E.
Principal Engineer
Attachments:
Appendix A
Summary of Field Density Tests
Appendix B
Plot Plan
2 OF 6
2;>
.
.
JOB NO.: 2208-CI-95
DATE: MAY 1, 1995
PROPOSED DEVELOPMENT
Single family residence is proposed for the subject site.
SCOPE OF WORK
Our scope of work was to observe the grading and perform compaction testing on
part-time basis.
DATES IOF OBSERVATION AND TESTING
The grading work was observed and field density tests were performed during March
31, April 3 and 4, 1995 by our field technician on part time basis.
GRADING EQUIPMENT
The grading work was performed using the following equipment:
(1) Track wheel dozer
(2) Fire hose
The Track wheel dozer and fire hose were used for grading, compaction, and
moisture conditioning,
3 OF 6
"
.
.
JOB NO.: 2208-CI-95
DATE: MAY 1,1995
GRADING AND FILL OPERATIONS
The lot was developed in minimal cuts and fills. Approximately 0.50 feet of fill was
placed on the north western portion of the building area and approximately 1 foot of fill was
placed on the south western portion of the building area.
The building area and at least five (5) feet beyond the proposed building Jines was
overexcavated to a minimum depth of 3 feet on the northern one half of the building area
arid to a minimum depth of 6 feet below original existing grade on the southern half of the
building area due to very wet soils conditions encountered in this area.
The bottom of overexcavations was scarified to a minimum depth of 12 inches and
was compacted to a minimum relative density of 90% prior to backfilling. The source of
saturation on the southern half of the proposed building area was not determined, however
it appears that the storm drain located at the northeastern corner of the lot has contributed
to the saturation of this area, therefore, drainage of the storm drain shall be diverted away
from the proposed building area to avoid saturation and potential settlement of building
area.
Compaction Density Tests were taken at the. bottom of the overexcavation' after
recompaction with results being at least 90% of the Maximum Dry Density with adequate
moisture.
Backfill soils were then placed in 6 to 8 inch lifts, well moisture conditioned, mixed
and compacted. Compaction Density Tests were taken at different intervals to verify the
moisture content and degree of compaction. Results of density test indicated a relative
density of at least 90% of the maximum dry density as determined by ASTM D 1557-78.
On site materials consisted of dark Brown medium to coarse silty sands on the
northern half of proposed building area and of golden Brown fine to medium silty sands on
the southern half of the building area.
4 OF 6
/'
~
, ,
.
.
JOB NO.: 2208-Cl-95
DATE: MAY 1,1995
FIELD DENSITY TESTING
In-place density tests were performed in accordance with the sand cone method,
ASTM D 1556-64 (74), and the maximum density of the backfill soils was obtained in
,accordance with ASTM D 1557-78.
CONCLUSIONS
o The bottom of the overexcavation and the backfill materials were
compacted to a minimum relative density of 90% as verified by field
density testing and probing.
o TIle above described grading has been completed in substantial compliance
with the grading code of the local building agencies.
o The rough graded pad appears to be adequate for the construction and
support of the proposed dwelling.
o All recommendations contained under grading and fill operations of this
report shall be adhered to during project development.
CLOSURE
Our findings and conclusions have been based on generally accepted engineering
practices. No further warranties are implied nor made.
5 OF 6
~
't
~-
.'
, .
.
.
JOB NO.: 2208-CI-95
DATE: MAY 1, 1995
MAX[[MUM DENSITY TEST RESULTS
soil type soil description
or location
(A)
optimum
moisture
Golden Brown fine to coarse 10.0 %
silty sands (SM)
(B)
-
Brown medium to coarse
silty sands (SM)
11.0 %
maximum dry
density pcf
12~.0 (pet)
.
138.0 (pet)
* Test performed in accordance with ASTM D 1557-78
6 OF 6
1
SUMMARY 0' FIELD DENS IT' TESTS
TEST COMMENTS DRY DENSITY MOISTURE%
DATE TEST LOCATION TYP AND R.C.
TEST ELV FIELD MAX. FIELD OPT
03/31 SOUTH BLDG BOTTOM A -6' 114.2 127.0 11.1 10.0 90
04/30 NORTH BLDG BOTTOM B -3' 127 .9 138.0 12.0 11.0 93
04/03 BLDG PAD BACKFILL A -4' 119.9 127.0 8.7 10.0 94
04/04 BLDG PAD BACKFILL B F.G 128.2 138.0 12.8 11. 0 93
'" _n
~
l
H;o,;sr
~
---'
,--
CARMEl\T A
"0 if'
......'tt
(jj'"
..f .
APPROXIMATE LOCATION OF STORM DRAIN PIPE
-qb,- APPROXIMATE LOCATION OF FIELD DENSITY TESTS
THIS IS NOT A PRECISE PLO'l' PLAN AND IS INTENDED TO LOCATE THE
APPROXIMATE LOCATIONS OF FIELD DENSITY TESTS ONLY AND SHALL NOT BE
USED FOR ANY OTHER PURPOSES 0 THIS OFFICE IS NOT RESPONSIBLE FOR ITS
ACCURACY.