ORDINANCE NO. 08-10
' AN ORDINANCE OF THE CITY COUNCIL OF THE CITY
OF TEMECULA AMENDING SECTION 15.04.030 OF THE
TEMECULA MUNICIPAL CODE RELATING TO THE
CALIFORNIA ELECTRICAL CODE
THE CITY COUNCIL OF THE CITY OF TEMECULA DOES HEREBY ORDAIN
AS FOLLOWS:
Section 1. Section 15.04.030 of Chapter 15.04 of Title 15 of the
Temecula Municipal Code is hereby amended by adding paragraphs F-J amending
California Electrical Code Sections 690.4(A), 690.14(A), 690.14(C)(2), 690.31(e) and
690 Part VI, as follows:
"F. 690.4 (A) is hereby amended to read as follows:
Only registered California Contractors License Board entities with a valid A, B, C-10 or
C-46 contractor license or the property owner shall install solar photovoltaic systems.
Valid copies of the entity's City of Temecula Business License and California
Contractors License Board license shall be submitted on the plans.
' Roof mounted systems -
Complete plans and substantiating design calculations shall be submitted showing
supporting member sizes, dimensions, materials and the loads which will be imposed
on the roof structure. Where the supporting framework of the modules or arrays are
shown as part of the laboratory approved system, additional design calculations will not
be required for the supporting framework of the modules or arrays provided as they are
included in the approved listing. Solar photovoltaic modules and/or arrays shall be
installed over only one roof covering unless approved by a California licensed engineer
for weight and wind uplift loads.
Solar systems not installed on roofs -
Foundation and/or footings size plans and substantiating design calculations shall be
submitted showing supporting member sizes, dimensions, materials and the loads
which will be imposed on the foundation or footings. Where the supporting framework
of the modules or arrays are shown as part of the laboratory approved system, design
calculations will not be required for the supporting framework of the modules or arrays
provided they are included in the approved listing.
Photovoltaic systems shall be marked for their use. Materials used for marking shall be
weather resistant and meet Underwriters Laboratories Marking and Labeling System
969 (UL969) standards for weather rating.
R:/Ords 2008/Ords 08-10 1
ACCESS, PATHWAYS AND SMOKE VENTILATION
r Access and spacing requirements shall be required in order to:
• Ensure access to the roof
• Provide pathways to specific areas of the roof
• Provide for smoke ventilation opportunities area
• Provide emergency egress from the roof
Designation of ridge, hip, and valley layout does not apply to roofs with 2-in-12 or less
pitch. All roof dimensions are measured to centerlines.
Roof access points shall be defined as areas where ladders are not placed over
openings (i.e., windows or doors) and are located at strong points of building
construction and in locations where they will not conflict with overhead obstructions (i.e.,
tree limbs, wires, or signs).
Residential Systems-Single and Two-Unit Residential Dwellings
1. Access/Pathways
Residential Buildings with hip roof layouts: Modules shall be located in a manner that
provides one (1) three-foot (3') wide clear access pathway from the eave to the ridge on
each roof slope where modules are located. The access pathway should be located at
a structurally strong location on the building (such as a bearing wall).
' Residential Buildings with a single ridge: Modules shall be located in a manner that
provides two (2) three-foot (3') wide access pathways from the eave to the ridge on
each roof slope where modules are located.
Hips and Valleys: Modules shall be located no closer than one and one half feet (18
inches) to a hip or a valley if modules are to be placed on both sides of a hip or valley.
If the modules are to be located on only one side of a hip or valley that is of equal length
then the modules may be placed directly adjacent to the hip or valley.
2. Smoke Ventilation
The modules shall be located no higher than three feet (3') below the ridge.
Commercial Buildings and Residential Housing comprised of Three (3) or More Units
Exception: If the Temecula fire department determines that the roof configuration is
similar to residential (such as in the case of townhouses, condominiums, or single family
attached buildings), the Temecula fire department may make a determination to apply
the residential access and ventilation requirements.
1. Access
There shall be a minimum six foot (6') wide clear perimeter around the edges of the
' roof.
RJOrds 200810rds 08-10 2
Exception: If either axis of the building is 150 feet or less, there should be a minimum
four feet (4') wide clear perimeter around the edges of the roof.
2. Pathways
Pathways shall be established in the design of the solar installation and meet the
following requirements:
a. Located over structural members
b. Centerline axis pathways shall be provided in both axis of the roof. Centerline
axis pathways shall run on structural members or over the next closest structural
member nearest to the center lines of the roof
c. Shall be a straight line not less than 4 feet (4') clear to skylights and/or ventilation
hatches
d. Shall be a straight line not less than 4 feet (4') clear to roof fire standpipes
e. Shall provide not less than 4 feet (4') clear around roof access hatch with at least
one not less than 4 feet (4') clear pathway to parapet or roof edge
3. Smoke Ventilation
a. Arrays shall be no greater than 150 by 150 feet in distance in either axis
b. Ventilation options between array sections shall be either:
1. A pathway 8 feet (8') or greater in width
2. 4 feet (4') or greater in width pathway and bordering on existing roof
with skylights or ventilation hatches
' 3. 4 feet (4') or greater in width pathway and bordering four feet (4') x 8
feet (8') "venting cutouts" every 20 feet (20') on alternating sides of the
pathway
G. Section 690.14 (A) is hereby amended to read as follows:
Disconnecting Means - The main electrical panel disconnecting means shall be
designed to shut off all power to all conductors inside structure(s). This includes both
Solar (Direct Current) and Utility (Alternating Current).
H. Section 690.14 (C) (2) is hereby amended to read as follows:
Marking Content and Format for Disconnects
• Marking content: CAUTION: SOLAR ELECTRIC SYSTEM CONNECTED
• Red background
• White lettering
• Minimum 3/8 inch height
• All capital letters
• Arial or similar font, non-bold
• Reflective, weather resistant material suitable for the environment - Materials used for
marking shall be weather resistant and meet Underwriters Laboratories Marking and
Labeling System 969 (UL969) standards for weather rating (durable adhesive materials
may meet this requirement).
R:/Ords 2008/Ords 08-10 3
The marking shall be placed immediately adjacent to the main service disconnect in a
location clearly visible from the main service disconnect.
1. Section 690.31 (E) is hereby amended to read as follows:
Direct-Current Photovoltaic Source and Output Circuits Inside a Building. Where direct
current photovoltaic source or output circuits of a utility-interactive inverter from a
building-integrated or other photovoltaic system are run inside a building or structure,
they shall be contained in metallic raceways or enclosures from the point of penetration
of the surface of the building or structure to the first readily accessible disconnecting
means. DC wiring shall be installed, to the maximum extent possible, along the bottom
of load-bearing members. The disconnecting means shall comply with 690.14(A)
through 690.14(D).
Conduit, wiring systems, and raceways for photovoltaic circuits shall be located as close
as possible to the ridge or hip or valley and from the hip or valley as directly as possible
to an outside wall to reduce trip hazards and maximize fire suppression ventilation
opportunities.
Conduit runs between sub arrays and to DC combiner boxes shall use design
guidelines that minimize total amount of conduit on the roof by taking the shortest path
from the array to the DC combiner box. The DC combiner boxes are to be located such
' that conduit runs are minimized in the pathways between arrays.
J. Section 690 Part VI is hereby amended to add the following:
Marking for Direct Current Conduit, Raceways, Enclosures, Cable Assemblies, and
Junction Boxes
Marking shall be required on all interior and exterior DC conduit, raceways, enclosures,
cable assemblies, and junction boxes. Marking shall be placed every 10 feet, at turns,
sweeps, immediately above and/or below penetrations and on all DC combiner and
junction boxes.
Marking Content and Format for Direct Current Conduit, Raceways, Enclosures, Cable
Assemblies, and Junction Boxes
• Marking content: CAUTION: SOLAR CIRCUIT
• Red background
• White lettering
• Minimum 3/8 inch height
• All capital letters
• Arial or similar font, non-bold
• Reflective, weather resistant material suitable for the environment - Materials used for
' marking shall be weather resistant and meet Underwriters Laboratories Marking and
RJOrds 2008/Ords 08-10 4
Labeling System 969 (UL969) standards for weather rating (durable adhesive materials
' may meet this requirement)."
Section 2. If any sentence, clause or phrase of this ordinance is for any
reason held to be unconstitutional or otherwise invalid, such decision shall not affect the
validity of the remaining provisions of this ordinance. The City Council hereby declares
that it would have passed this ordinance and each sentence, clause or phrase thereof
irrespective of the fact that any one or more sentences, clauses or phrases be declared
unconstitutional or otherwise invalid.
Section 3. The City Clerk of the City of Temecula shall certify to the
passage and adoption of this Ordinance and shall cause the same or a summary
thereof to be published and posted in the manner required by law.
PASSED, APPROVED, AND ADOPTED by the City Council of the City of
Temecula this 18th day of November, 2008.
\ ~ lV
Michael S. Na ar, Mayor
' ATTEST:
Susan W. Jones, MMC
CI
[SEAL]
1
RJOrds 2008/Ords 08-10 5
STATE OF CALIFORNIA )
COUNTY OF RIVERSIDE ) ss
CITY OF TEMECULA )
I, Susan W. Jones, MMC, City Clerk of the City of Temecula, do hereby certify that
the foregoing Ordinance No. 08-10 was duly introduced and placed upon its first reading
at a meeting of the City Council of the City of Temecula on the 28th day of October, 2008,
and that thereafter, said Ordinance was duly adopted by the City Council of the City of
Temecula at a meeting thereof held on the 18th day of November, 2008, by the following
vote:
AYES: 4 COUNCIL MEMBERS: Comerchero, Edwards, Washington,
Naggar
NOES: 0 COUNCIL MEMBERS: None
ABSENT: 1 COUNCIL MEMBERS: Roberts
ABSTAIN: 0 COUNCIL MEMBERS: None
Susan . Jones, MMC
City Clerk
1
RJOrds 2008/Ords 08-10 6