HomeMy WebLinkAbout08_026 DH ResolutionDH RESOLUTION NO. 08-026
A RESOLUTION OF THE DIRECTOR OF PLANNING OF
THE CITY OF TEMECULA APPROVING PLANNING
APPLICATION NO. PA08.0148, A MINOR MODIFICATION
TO AN APPROVED DEVELOPMENT PLAN TO
ELIMINATE THE UNDERGROUND PARKING LOT AND
REDUCE THE BUILDING HEIGHT AND SQUARE
FOOTAGE OF THE JAMES WEBB BUILDING LOCATED
AT 27423 YNEZ ROAD IN THE TOWER PLAZA CENTER
Section 1. Procedural Findings. The Director of Planning of the City of
Temecula does hereby find, determine and declare that:
A. On June 6, 2007, the Planning Commission approved Planning
Application No. PA06-0187, a Development Plan for a three-story, 14,093 square foot
office building with a 7,369 square foot underground parking structure on 0.53 acres
located at 27423 Ynez Road, and Planning Application No. PA07-0049, a Minor
Exception to allow for a 15 percent building height increase from 50' to 57'4."
B. On June 26, 2008, Walt Allen Architects filed Planning Application No.
PA08-0148, a Minor Modification Application in a manner in accord with the City of
Temecula General Plan and Development Code.
C. The Application was processed including, but not limited to a public notice,
in the time and manner prescribed by State and local law.
D. The Director of Planning, at a regular meeting, considered the Application
and environmental review on December 18, 2008, at a duly noticed public hearing as
prescribed by law, at which time the City staff and interested persons had an
opportunity to and did testify either in support or in opposition to this matter.
E. At the conclusion of the Director's Hearing and after due consideration of
the testimony, the Director of Planning approved Planning Application No. PA08-0148
subject to Conditions of Approval, after finding that the project proposed in Planning
Application No. PA08-0148, conformed to the City of Temecula's General Plan and
Development Code.
Section 2. Further Findings. The Director of Planning, in approving Planning
Application No. PA08-0148, hereby makes the following findings as required by
Development Code Section 17.05.010.F, Minor Modification.
A. The proposed use is in conformance with the General Plan for Temecula
and with all applicable requirements of State law and other Ordinances of the City;
The proposal is consistent with the General Plan land use designation, and with
the standards and requirements for the Community Commercial zoning district.
The proposed office use is permitted in the land use designation standards
GAPLANNING\2008\PA08-0148 James Webb Building Minor MOD\Planning\DH Reso.doc
contained in the General Plan and Development Code. The site is properly
planned and zoned, and as conditioned, is physically suitable for the type of
development proposed. The proposed project, as conditioned, is consistent with
other applicable requirements of state law and local ordinances, including the
California Environmental Quality Act (CEQA) and all applicable Fire and Building
Codes.
B. The overall development of the land is designed for the protection of the
public health, safety, and general welfare;
The proposed project is consistent with the development standards outlined in
the City of Temecula Development Code. The proposed site layout for the
project has been reviewed utilizing the Citywide Design Guidelines and
development standards for commercial office buildings. The proposed project
meets the standards for circulation, site plan design, and landscaping. The
project has been found to be consistent with all applicable policies, guidelines,
standards and regulations intended to ensure that the development will be
constructed and function in a manner consistent with the public health, safety
and welfare.
Section 3. Conditions. The Director of Planning of the City of Temecula
approves Planning Application No. PA08-0148, a Minor Modification to eliminate the
underground parking structure and reduce the building height and square footage of the
James Webb building, located at 27423 Ynez Road, subject to the Conditions of
Approval set forth on Exhibit A, attached hereto, and incorporated herein by.this
reference.
Section 4. PASSED, APPROVED AND ADOPTED by the City of Temecula
Director of Planning this 18th day of December 2008.
Debbie bnoske, Director of Planning
I, Kathy Simpkins, Secretary of the Temecula Director's Hearing, do hereby
certify that the forgoing DH Resolution No. 08-026 was duly and regularly adopted by
the Director of Planning of the City of Temecula at a regular meeting thereof held on
the 18th day of December 2008.
thy i ns, Se eta
G:\PLANNING\2008\PA08-0148 James Webb Building Minor MOD\Planning\DH Reso.doc
EXHIBIT A
DRAFT CONDITIONS OF APPROVAL
SCANNED:
G DRIVE:
PERMITS PLUS:
INITIALS:
PLANNER:
EXHIBIT A
CITY OF TEMECULA
DRAFT CONDITIONS OF APPROVAL
Planning Application No.: PA08-0148
Project Description: A Minor Modification to an approved Development Plan to eliminate
the underground parking lot and reduce the building height and
square footage of the James Webb building located at 27423 Ynez
Road in the Tower Plaza Center
Assessor's Parcel No.
MSHCP Category:
DIF Category:
TUMF Category:
Approval Date:
Expiration Date:
PLANNING DEPARTMENT
921-260-022
Commercial
Office
Service Commercial/Office
December 18, 2008
N/A
Within 48 Hours of the Approval of This Project
PL-1. The applicant shall review and sign the Acceptance of Conditions of Approval
document that will be provided by the Planning Department staff and return the
document with an original signature to the Planning Department.
General Requirements
PL-2. The applicant and owner of the real property subject to this condition shall hereby
agree to indemnify, protect, hold harmless, and defend the City with Legal Counsel of
the City's own selection from any and all claims, actions, awards, judgments, or
proceedings against the City to attack, set aside, annul, or seek monetary damages
resulting, directly or indirectly, from any action in furtherance of and the approval of the
City, or any agency or instrumentality thereof, advisory agency, appeal board or
legislative body including actions approved by the voters of the City, concerning the
Planning Application. The City shall be deemed for purposes of this condition, to
include any agency or instrumentality thereof, or any of its elected or appointed
officials, officers, employees, consultants, contractors, legal counsel, and agents. City
shall promptly notify both the applicant and landowner of any claim, action, or
proceeding to which this condition is applicable and shall further cooperate fully in the
defense of the action. The City reserves the right to take any and all action the City
deems to be in the best interest of the City and its citizens in regards to such defense.
PL-3. The permittee shall obtain City approval for any modifications or revisions to the
approval of this project.
PL-4. The expiration of the application is subject to the underlying Development Plan, PA06-
0187, or expiration date of subsequent extension of time approvals.
PL-5. The development of the premises shall substantially conform to the approved site plan
and elevations contained on file with the Planning Department for PA08-0148.
PL-6. Unless amended herein, all Conditions of Approval for the approved Development Plan,
PA06-0187, shall remain in effect and apply to the project.
PL-7. Parking for the project shall be shared across the site, including parking spaces in all
lots that are a part of the project.
PL-8. If construction is phased, a construction staging area plan or phasing plan for
construction equipment and trash shall be approved by the Director of Planning.
Prior to Release of Power, Building Occupancy or Any Use Allowed by This Permit
PL-9. An applicant shall submit a letter of substantial conformance, subject to field verification
by the Planning Director or his/her designee. Said letter of substantial conformance
shall be prepared by the project designer and shall indicate that all plant materials and
irrigation system components have been installed in accordance with the approved final
landscape and irrigation plans. If a certificate of use and occupancy is not required for
the project, such letter of substantial conformance shall be submitted prior to
scheduling for the final inspection.
PL-10. All of the foregoing conditions shall be complied with prior to occupancy or any use
allowed by this permit.
BUILDING AND SAFETY DEPARTMENT
B-1. Unless amended herein, all Conditions of Approval for PA06-0187 shall remain in effect
and apply to the project.
COMMUNITY SERVICES DEPARTMENT
CS-1. Unless amended herein, all Conditions of Approval for PA06-0187 shall remain in effect
and apply to the project.
FIRE PREVENTION
General Requirements
F-1. Final fire and life safety conditions will be addressed when building plans are reviewed
by the Fire Prevention Bureau. These conditions will be based on occupancy, use, the
California Building Code (CBC), California Fire Code (CFC), and related codes which
are in force at the time of building plan submittal.
F-2. The Fire Prevention Bureau is required to set a minimum fire flow for the construction of
all commercial buildings per CFC Appendix B. The developer shall provide for this
project, a water system capable of delivering 4,000 GPM at 20-PSI residual operating
pressure for a 4-hour duration. The fire flow as given above has taken into account all
information as provided (CFC Appendix B and Temecula City Ordinance 15.16.020,
Section R).
F-3. The Fire Prevention Bureau is required to set minimum fire hydrant distances per CFC
Appendix C. A combination of on-site and off site 6" x 4" x 2-2'/2" outlets on a looped
system shall be located on fire access roads and adjacent to public streets. Hydrants
shall be spaced at 350 feet apart, at each intersection and shall be located no more
than 210 feet from any point on the street or Fire Department access road(s) frontage
to a hydrant. The required fire flow shall be available from any adjacent hydrants in the
system (CFC Appendix C and Temecula City Ordinance 15.16.020, Section R).
F-4. As required by the California Fire Code, when any portion of the facility is in excess of
150 feet from a water supply on a public street, as measured by an approved route
around the exterior of the facility, on-site fire hydrants and mains capable of supplying
the required fire flow shall be provided (CFC Chapter 5, Section 508.5).
F-5. If construction is phased, each phase shall provide approved access and fire protection
prior to any building construction (CFC Chapter 5, Section 503.4).
Prior to Issuance of Grading Permit(s)
F-6. Fire apparatus access roads shall be designed and maintained to support the imposed
loads of fire apparatus and shall be with a surface to provide all-weather driving
capabilities. Access roads shall be 80,000 lbs. GVW with a minimum of AC thickness
of .25 feet. In accordance with Section 1410.1, prior to building construction, all
locations where structures are to be built shall have fire apparatus access roads (CFC
Chapter 5, Section 503.2, 503.4 and City Ordinance 15.16.020 Section E).
F-7. Fire Department vehicle access roads shall have an unobstructed width of not less than
24 feet and an unobstructed vertical clearance of not less than 13 feet 6 inches (CFC
Chapter 5, Section 503.2, 503.4 and City Ordinance 15.16.020 Section E).
F-8. Dead end roadways and streets in excess of 150 feet which have not been completed
shall have a turnaround capable of accommodating fire apparatus (CFC Chapter 5,
Section 503.2.5 and City Ordinance 15.16.020 Section E).
Prior to Issuance of Building Permit(s)
F-9. The developer shall furnish one copy of the water system plans to the Fire Prevention
Bureau for approval prior to installation for all private water systems pertaining to the
fire service loop. This also applies to laterals coming into the building for the fire
sprinkler system if no on site hydrants are required. Plans shall be signed by a
registered civil engineer, contain a Fire Prevention Bureau approval signature block,
and conform to hydrant type, location, spacing and minimum fire flow standards.
Hydraulic calculations will be required with the underground submittal to ensure fire
flow requirements are being met for the on-site hydrants. The plans must be submitted
and approved prior to building permit being issued (CFC Chapter 14, Section 1412 and
Chapter 5, Section 501.3).
F-10. Fire sprinkler risers shall not be obstructed in any manner. The fire system riser is to
be provided with eighteen (18) inch clearance to each side and to the front of the
system riser, access shall be provided by means of a door with the minimum
dimensions two (2) feet six (6) inches wide by six (6) feet eight (8) inches tall from the
exterior of the building directly to the riser as approved by the Chief. The fire system
riser room shall not share with any other equipment (i.e., mechanical, electrical, etc.).
The main fire alarm control panel shall also be placed in the riser room.
F-11. Fire sprinkler plans shall be submitted to the Fire Prevention Bureau for approval.
Three sets of sprinkler plans must be submitted by the installing contractor to the Fire
Prevention Bureau. These plans must be submitted prior to the issuance of building
permit.
F-12. Fire alarm plans shall be submitted to the Fire Prevention Bureau for approval. Three
sets of alarm plans must be submitted by the installing contractor to the Fire Prevention
Bureau. The fire alarm system is required to have a dedicated circuit from the house
panel. These plans must be submitted prior to the issuance of building permit.
Prior to Issuance of Certificate of Occupancy
F-13. Hydrant locations shall be identified by the installation of reflective markers (blue dots)
per City Ordinance 15.16.020 Section E.
F-14. New and existing buildings shall have approved address numbers, building numbers or
approved building identification placed in a position that is plainly legible and visible
from the street or road fronting the property. These numbers shall contrast with their
background. Commercial buildings shall have a minimum of 12-inch numbers with
suite numbers being a minimum of six inches in size. All suites shall have a minimum
of 6-inch high letters and/or numbers on both the front and rear doors (CFC Chapter 5,
Section 505.1 and City Ordinance 15.16.020 Section E).
F-15. A "Knox-Box" shall be provided. The Knox-Box shall be installed a minimum of six feet
in height and be located to the right side of the fire riser sprinkler room (CFC Chapter 5,
Section 506).
F-16. The applicant shall prepare and submit to the Fire Department for approval, a site plan
designating fire lanes with appropriate lane painting and/or signs (CFC Chapter 5,
Section 503.3).
F-17. A simple plot plan and a simple floor plan, each as an electronic file of the DWG
format, must be submitted to the Fire Prevention Bureau. Contact Fire Prevention for
approval of alternative file formats which may be acceptable.
PUBLIC WORKS DEPARTMENT
General Requirements
PW-1. Unless otherwise noted, all conditions shall be completed by the developer at no cost
to any Government Agency. It is understood that the developer correctly shows on the
site plan all existing and proposed property lines, easements, traveled ways,
improvement constraints and drainage courses, and their omission may require the
project to be resubmitted for further review and revision.
PW-2. A Grading Permit for precise grading, including all on-site flat work and improvements,
shall be obtained from the Department of Public Works prior to commencement of any
construction outside of the City-maintained street right-of-way.
PW-3. An Encroachment Permit shall be obtained from the Department of Public Works prior
to commencement of any construction within an existing or proposed City right-of-way.
PW-4. All improvement plans shall be coordinated for consistency with adjacent projects and
existing improvements contiguous to the site and shall be submitted on standard 24" x
36" City of Temecula mylars.
PW-5. The project shall include construction-phase pollution prevention controls and
permanent post-construction water quality protection measures into the design of the
project to prevent non-permitted runoff from discharging off site or entering any storm
drain system or receiving water.
PW-6. A Water Quality Management Plan (WQMP) must be accepted by the City prior to the
initial grading plan check. The WQMP will be prepared by a registered civil engineer
and include site design Best Management Practices, (BMPs) source controls, and
treatment mechanisms.
Prior to Issuance of Grading Permit(s)
PW-7. A permit from Riverside County Flood Control and Water Conservation District is
required for work within their right-of-way.
PW-8. A grading plan shall be prepared by a registered civil engineer in accordance with City
of Temecula standards, and shall be reviewed and approved by the Department of
Public Works prior to the commencement of grading. The grading plan shall include all
necessary erosion control measures needed to adequately protect the site (public and
private) and adjoining properties from damage due to erosion.
PW-9. The developer shall post security and enter into an agreement guaranteeing the
grading and erosion control improvements in conformance with applicable City
Standards and subject to approval by the Department of Public Works in accordance
with Grading Ordinance Section 18.24.120.
PW-10. A Soils Report shall be prepared by a registered soil or civil engineer and submitted to
the Department of Public Works with the initial grading plan check. The report shall
address all soil conditions of the site, and provide recommendations for the
construction of engineered structures and pavement sections.
PW-11. A Geological Report shall be prepared by a qualified engineer or geologist and
submitted to the Department of Public Works with the initial grading plan check. The
report shall address special study zones and the geological conditions of the site, and
shall provide recommendations to mitigate the impact of ground shaking and
liquefaction.
PW-12. The developer shall have a Drainage Study prepared by a registered civil engineer in
accordance with City Standards identifying storm water runoff expected from this site
and upstream of this site. The study shall identify all existing or proposed public or
private drainage facilities intended to discharge this runoff. The study shall also
analyze and identify impacts to downstream properties and provide specific
recommendations to protect the properties and mitigate any impacts. Any upgrading or
upsizing of downstream facilities, including acquisition of drainage or access
easements necessary to make required improvements, shall be provided by the
developer.
PW-13. Construction-phase pollution prevention controls shall be consistent with the City's
Grading, Erosion and Sediment Control Ordinance and associated technical manual,
and the City's standard notes for Erosion and Sediment Control.
PW-14. The project shall demonstrate coverage under the State NPDES General Permit for
Construction Activities by providing a copy of the Waste Discharge Identification
Number (WDID) issued by the State Water Resources Control Board (SWRCB). A
Stormwater Pollution Prevention Plan (SWPPP) shall be available at the site throughout
the duration of construction activities.
PW-15. As deemed necessary by the Department of Public Works, the developer shall receive
written clearance from the San Diego Regional Water Quality Board, Riverside County
Flood Control and Water Conservation District, Planning Department, or other affected
agencies.
PW-16. The developer shall comply with all constraints which may be shown upon an
Environmental Constraint Sheet (ECS) recorded with any underlying maps related to
the subject property.
PW-17. The applicant shall comply with the provisions of Chapter 8.24 of the Temecula
Municipal Code (Habitat Conservation) by paying the appropriate fee set forth in that
ordinance or by providing documented evidence that the fees have already been paid.
PW-18. The developer shall obtain letters of approval for any off site work performed on
adjoining properties. The letters shall be in format as directed by the Department of
Public Works.
PW-19. The developer must comply with the requirements of the National Pollutant Discharge
Elimination System (NPDES) permit from the State Water Resources Control Board.
No grading shall be permitted until an NPDES Notice of Intent (NOI) has been filed or
the project is shown to be exempt.
Prior to Issuance of Building Permit(s)
PW-20. Improvement plans shall conform to applicable City of Temecula Standards subject to
approval by the Department of Public Works. The following design criteria shall be
observed:
Flowline grades shall be 0.5% minimum over P.C.C. and 1.00% minimum over
A.C. paving.
b. Concrete sidewalks and ramps shall be constructed along public street frontages
in accordance with City of Temecula Standard Number. 400.
c. Improvement plans shall extend 300 feet beyond the project boundaries.
d. Public street improvement plans shall include plans and profiles showing existing
topography, utilities, proposed centerline, top of curb and flowline grades.
PW-21. The developer shall construct all public improvements outlined in these conditions to
City of Temecula General Plan standards unless otherwise noted. Plans shall be
reviewed and approved by the Department of Public Works.
PW-22. Improve Ynez Road from the northerly parcel boundary to the southerly boundary for
Parcel 2 (Arterial Highway Standards-110'R/W) to include installation of sidewalk and
utilities (including but not limited to water and sewer).
PW-23. Ynez Road (Arterial Highway Standards - 110' R/W) along entire parcel boundary to
include dedication of half-width street right-of-way.
PW-24. The developer shall construct all public improvements in conformance with applicable
City Standards and subject to approval by the Department of Public Works including
street improvements, which may include, but not limited to, pavement, curb and gutter,
median, sidewalk, drive approaches; streetlights, signing, striping, traffic signal
systems, other traffic control devices as appropriate; sewer and domestic water
systems; under grounding of proposed utility distribution lines; and storm drain facilities.
PW-25. A construction area Traffic Control Plan shall be designed by a registered civil or traffic
engineer and reviewed by the Department of Public Works for any street closure and
detour or other disruption to traffic circulation as required by the Department of Public
Works.
PW-26. The building pad shall be certified to have been substantially constructed in accordance
with the approved Precise Grading Plan by a registered civil engineer, and the soil
engineer shall issue a Final Soil Report addressing compaction and site conditions.
PW-27. The developer shall pay to the City the Public Facilities Development Impact Fee as
required by, and in accordance with, Chapter 15.06 of the Temecula Municipal Code
and all Resolutions implementing Chapter 15.06.
PW-28. The developer shall pay to the City the Western Riverside County Transportation
Uniform Mitigation Fee (TUMF) Program as required by, and in accordance with,
Chapter 15.08 of the Temecula Municipal Code and all Resolutions implementing
Chapter 15.08.
Prior to Issuance of Certificate of Occupancy
PW-29. The project shall demonstrate the pollution prevention BMPs outlined in the WQMP
have been constructed and installed in conformance with approved plans and are ready
for immediate implementation.
PW-30. As deemed necessary by the Department of Public Works the developer shall receive
written clearance from Rancho California Water District, Eastern Municipal Water
District, or other affected agencies.
PW-31. All public improvements shall be constructed and completed per the approved plans
and City standards to the satisfaction of the Department of Public Works.
PW-32. The existing improvements shall be reviewed. Any appurtenance damaged or broken
shall be repaired or removed and replaced to the satisfaction of the Department of
Public Works.
PW-33. All necessary certifications and clearances from engineers, utility companies and public
agencies shall be submitted as required by the Department of Public Works.